F: Mila manandrana tariby 220 kV aho, 8 km ny halavany. Inona ny naoty SR ilaiko?
A: 7-dingana fandrefesana: mamaritra ny fepetra takiana amin'ny fitsapana → kajy C → tombantombana L → kajy f_res → manamarina ny naoty → avereno → farany.
Dingana-an'ny-dingana - 220 kV tariby, 8 km:
1. IEC 60840: V_test=2.0 × 127 kV=254 kV. Faharetana 60 min.
2. C ≈ 8 km × 0,2 μF/km=1.6 μF.
3. Diniho ny 3 × 100 kV/2 A reactors mifanitsy: L=26.7 H, f=24.4 Hz.
4. Ankehitriny amin'ny 254 kV: I=V × 2πf × C=6.9 A. Fa 3×2A → 6A total → TSY OK.
5. Havaozina ho 3×100 kV/4 A réactors: total I=12 A → OK. P_in=254×6.9/35=50 kW.
6. Lanja manontolo: 3×450 kg + 200 + 150 + 100=~1.800 kg.
Famintinana habe ho an'ny toe-javatra mahazatra:
|
Tantara |
V_test (kV) |
C (μF) |
f (Hz) |
Recommended System |
|
Cable 33 kV, 3 km |
48 |
0.6 |
45 |
60 kV/2A × 1, 5 kW |
|
Cable 110 kV, 5 km |
160 |
1.0 |
24 |
200 kV/4A × 2, 20 kW |
|
Cable 220 kV, 8 km |
254 |
1.6 |
24 |
300 kV/4A × 3, 50 kW |
|
Cable 400 kV, 5 km |
330 |
1.0 |
48 |
400 kV/2A × 2, 25 kW |
|
GIS 245 kV, 10 bay |
230 |
0.05 |
80 |
300 kV/1A ×2, 5 kW |
|
Generator 100 MVA |
28 |
2.5 |
45 |
30 kV/5A, 10 kW |
Fampahatsiahivana mitsikera:
• +20% margin eo amin'ny reactor voltage rating. +30% margin amin'ny ankehitriny.
• Raha P_in> 100 kW, dia diniho ny fizarana fizarana (avela amin'ny ankamaroan'ny fenitra).
• Ny Q tena izy dia mety ho ambany noho ny tombantombana - drafitra mpandala ny nentin-drazana hisorohana ny tsy fahombiazan'ny sehatra.